116 HX7+ ASD Installation and Operation Manual
BIN Torque Reference Setpoint #2
Program Torque Setting Setpoints BIN
This parameter is used to set the gain and bias of the binary input when the
discrete input terminals are used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given binary input signal.
See BIN Speed Reference #1 for further information on this setting.
This parameter sets BIN Torque Reference Setpoint #2 and is the output
torque value that is associated with setting of BIN Speed Reference #2 while
operating in the Torque control mode.
Direct Access Number — F233
Parameter Type — Numerical
Factory Default 100.00
Changeable During Run — Ye s
Minimum — -250.0
Maximum — 250.0
Units — %
PG Speed Reference #1
Program Frequency Setting Speed Reference Setpoints PG
This parameter is used to set the gain and bias of the PG input terminal when a
shaft-mounted encoder is used as the feedback transducer while operating in the
Speed Control mode.
Note: The ASD-Multicom Option Board and the HS35 Encoder is
required for system operation using the PG input speed control.
PG Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the PG input terminal:
•Program Fundamentals Standard Mode Selection Frequency
Mode #1 Pulse Input Option.
•Program Fundamentals Standard Mode Selection Command
Mode (any setting).
•Set PG Speed Reference #1 (F234) — the input pulse count rate that
represents PG Speed Frequency #1.
•Set PG Speed Frequency #1 (F235).
•Set PG Speed Reference #2 (F236) — the input pulse count rate that
represents PG Speed Frequency #2.
•Set PG Speed Frequency #2 (F237).
•Provide a Run command (F and/or R).
Once set, as the PG pulse count rate changes, the output frequency of the ASD
will vary in accordance with the above settings.
This parameter sets PG Speed Reference #1 and is the input pulse count rate
that is associated with the setting of PG Speed Frequency #1 while operating
in the Speed Control mode.
Direct Access Number — F234
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
F233 F234