HX7+ ASD Installation and Operation Manual 117
PG Speed Frequency #1
Program Frequency Setting  Speed Reference Setpoints PG
This parameter is used to set the gain and bias of the PG input terminal when a 
shaft-mounted encoder is used as the feedback transducer while operating in the 
Speed Control mode.
See PG Speed Reference #1 (F234) for further information on this setting.
This parameter sets PG Speed Frequency #1 and is the frequency that is 
associated with the setting of PG Speed Reference #1 while operating in the 
Speed Control mode.
Direct Access Number —  F235
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — -Max. Freq. (F011)
Maximum — Max. Freq. (F011)
Units — Hz
PG Speed Reference #2
Program Frequency Setting  Speed Reference Setpoints PG
This parameter is used to set the gain and bias of the PG input terminal when a 
shaft-mounted encoder is used as the feedback transducer while operating in the 
Speed Control mode.
See PG Speed Reference #1 for further information on this setting when used 
for Speed control.
This parameter sets the PG input level that is associated with PG Speed 
Frequency #2 while operating in the Speed control mode.
Direct Access Number —  F236
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Ye s
Minimum — -100.0
Maximum — 100.0
Units — %
PG Speed Frequency #2
Program Frequency Setting  Speed Reference Setpoints PG
This parameter is used to set the gain and bias of the PG input terminal when a 
shaft-mounted encoder is used as the feedback transducer while operating in the 
Speed Control mode.
See PG Speed Reference #1 for further information on this setting when used 
for Speed control.
This parameter sets PG Speed Frequency #2 and is the frequency that is 
associated with the setting of PG Speed Reference #2 while operating in the 
Speed Control mode.
Direct Access Number —  F237
Parameter Type — Numerical
Factory Default — 80.00
Changeable During Run — Ye s
Minimum — -Max. Freq. (F011)
Maximum — Max. Freq. (F011)
Units — Hz
Startup Frequency
Program Special Control Frequency Control
The output of the drive will remain at 0.0 Hz until the programmed speed value 
exceeds this setting during startup. Once exceeded during startup, the output 
frequency of the drive will accelerate to the programmed setting.
Output frequencies below the Startup Frequency will not be output from the 
drive during startup. However, once reaching the Startup Frequency, speed 
values below the Startup Frequency may be output from the drive.
Direct Access Number —  F240
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 10.0
Units — Hz
F235 F240