HX7+ ASD Installation and Operation Manual 153
Voltage Compensation Coefficient for Dead Time
Program Special Control Special Parameters
This parameter adjusts the degree of voltage compensation during dead time by
increasing or decreasing the on-time of the programmed PWM just prior to the
start of the dead time.
Direct Access Number — F488
Parameter Type — Numerical
Factory Default 163.8
Changeable During Run — Ye s
Minimum — 1.64
Maximum — 327.6
Dead Time Compensation (Enable)
Program Special Control Special Parameters
This parameter Enables/Disables the Dead Time Compensation function. The
Dead Time Compensation feature provides a smoothing of the on-off IGBT
signal that feeds the Gate Driver board during the off portion of the on-off
cycle.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F489
Parameter Type — Selection List
Factory Default Enabled
Changeable During Run — Ye s
Dead-time Compensation Bias
Program Special Control Special Parameters
This parameter sets a bias for the Dead-time Compensation function. The
Dead-time Compensation feature provides a smoothing of the on-off IGBT
signal that feeds the Gate Driver board.
Direct Access Number — F490
Parameter Type — Numerical
Factory Default 0.000
Changeable During Run — Ye s
Minimum — -32.768
Maximum — 32.767
Switching Frequency of Current/Voltage Control
Program Special Control Special Parameters
This parameter sets the threshold frequency at which ASD control is switched
between Current-control and Voltage -control.
Direct Access Number — F491
Parameter Type — Numerical
Factory Default 40.00
Changeable During Run — Ye s
Minimum — 10.00
Maximum — 60.00
Units — Hz
Accel #2 Time
Program Special Control Accel/Decel #1-#4
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to
the Maximum Frequency for the #2 Acceleration profile. The accel/decel
pattern may be set using F502. The minimum accel/decel time may be set using
F508.
This setting is also used to determine the acceleration rate of the Motorized Pot
function.
Note: An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.
Direct Access Number — F500
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 0.1
Maximum — 6000
Units — Seconds