154 HX7+ ASD Installation and Operation Manual
Decel #2 Time
Program Special Control Accel/Decel #1 – #4
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The accel/
decel pattern may be set using F502. The minimum accel/decel time may be set
using F508.
This setting is also used to determine the deceleration rate of the Motorized
Pot function.
Note: A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.
Direct Access Number — F501
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 0.1
Maximum — 6000
Units — Seconds
F501 F501