HX7+ ASD Installation and Operation Manual 183
LOD Restart Delay Time
Program Special Control Low Output Disable
The Low Output Disable Restart Delay Time sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Direct Access Number — F737
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Minimum Carrier Frequency 2.2 kHz
Program Special Control Carrier Frequency
This parameter is used to increase the carrier frequency as a function of the
F300 parameter setting.
With this parameter (F738) Enabled and F300 set to a value less than 2.2 kHz,
F300 is increased to 2.2 kHz.
With this parameter (F738) Enabled and F300 set to a value equal to or greater
than 2.2 kHz, F300 is unchanged.
With this parameter (F738) Disabled, F300 is not affected.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F738
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — Ye s
Rocking Start
Program Special Control Special Parameters
This parameter setting is used when starting a large load very slowly is
required.
An on/off 20 Hz output signal is applied to the motor for the duration of 0.5
seconds times the number setting of this parameter (i.e., setting 3 = 1.5 seconds
of 20 Hz on/off output signal).
Upon completion of the Rocking Start the programmed acceleration rate
resumes.
Direct Access Number — F739
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Ye s
Minimum — 0
Maximum — 255
Units — Seconds
Over-Heat Stall
Program Protection Stall
This parameter Enables/Disables the Over-Heat Stall function.
Alarms and trips are unaffected by this setting.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F740
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — Ye s
F737 F740