186 HX7+ ASD Installation and Operation Manual
Frequency Point Selection
Program Communication Communication Reference Adjust
This parameter enables the communications reference for scaling by selecting
an input type.
See F811F814 for further information on this setting.
Note: Scaling the communications signal is not required for all
applications.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — Disabled
1 — Common Serial (TTL)
2 — RS232/RS485
3 — Communication Card
Direct Access Number — F810
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — Ye s
Communications Speed Reference #1
Program Communication Communication Reference Adjust
When enabled at F810, this parameter is used to allow the user to set the gain
and bias of the speed control input to the drive when the speed control signal is
received via the source selected at
F810.
Communications Input Speed Control Setup
Perform the following setup to allow the system to receive control input via
Communications:
•Set Communications Speed Reference #1 (F811) — the input signal
that represents BIN Speed Frequency #1.
•Set Communications Speed Frequency #1 (F812).
•Set Communications Speed Reference #2 (F813) — the input signal
that represents BIN Speed Frequency #2.
•Set Communications Speed Frequency #2 (F814).
•Provide a Run command (F and/or R).
Once set, as the input signal value changes, the output frequency of the drive
will vary in accordance with the above settings.
This parameter sets the Communications Speed Reference #1 input value that
represents Communications Speed Frequency #1. This value is entered as 0 to
100% of the Communications Speed Reference #1 input value range.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F811
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 100.0
Units — %
F810 F811