HX7+ ASD Installation and Operation Manual 187
Communications Speed Frequency #1
Program Communication Communication Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See F811 for further information on this setting.
This parameter sets Communications Speed Frequency #1 and is the
frequency that is associated with the setting of Communications Speed
Reference #1.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F812
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Communications Speed Reference #2
Program Communication Communication Reference Adjust
This parameter is used to set the gain and bias of the Communications Speed
Reference #2 speed control input.
See F811 for further information on this setting.
This parameter sets the Communications Speed Reference #2 input value that
represents Communications Speed Frequency #2. This value is entered as 0 to
100% of the Communications Speed Reference #2 input value range.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F813
Parameter Type — Numerical
Factory Default 100.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 100.0
Units — %
Communications Speed Frequency #2
Program Communication Communication Reference Adjust
This parameter is used to set the gain and bias of the Communications Speed
Reference #2 speed control input.
See F811 for further information on this setting.
This parameter sets Communications Speed Frequency #2 and is the
frequency that is associated with the setting of Communications Speed
Reference #2.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F814
Parameter Type — Numerical
Factory Default 80.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
RS232/RS485 Baud Rate
Program Communication Communication Settings
This parameter sets the RS232/RS485 baud rate.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — 1200
1 — 2400
2 — 4800
3 — 9600
4 — 19200
5 — 38400
Direct Access Number — F820
Parameter Type — Selection List
Factory Default 9600
Changeable During Run — Ye s
F812 F820