HX7+ ASD Installation and Operation Manual 193
Table 15 shows the output selections for the AM, FM, FP, and Analog 1 & 2 terminals. The magnitude
of the AM and FM output signals at full-scale is selection-specific and may be adjusted (see
F671
and
F006) to fit application-specific requirements.
The column on the right side of Table 15 shows the actual AM and FM outputs for a keypad display of
100%.
Table 15. Output terminal selections for the AM, FM, FP, and Analog 1 & 2 terminals.
Function
AM/FM Output Value at 100%
Keypad-Displayed Output
Output Frequency (FM and FP default setting)
Maximum Frequency
Frequency Reference
Output Current (AM default setting)
150%DC Bus Voltage
Output Voltage (Analog 1 default setting)
Post-compensation Frequency (Analog 2 default setting)
Maximum FrequencySpeed Feedback (realtime)
Speed Feedback (1 sec filter)
Torque
150%
Torque Command
Internal Torque Base
Torque Current
Excitation Current
PID Feedback Value Maximum Frequency
Motor Overload Ratio Motor Overload Trip-Point Setting
ASD Overload Ratio ASD Overload Trip-Point Setting
PBR (DBR) Overload Ratio DBR Overload Trip Point Setting
PBR (DBR) Load Ratio Maximum DBR Duty Cycle
Input Power
1.73 * input voltage * ASD rated current
Output Power
Peak Output Current
150%
Peak DC Bus Voltage
PG Counter
32767 Encoder Pulses
Position Pulse
RR Input
100%
VI/II Input
RX Input
RX2 Input
FM Output (used for factory testing only)
AM Output (used for factory testing only)
Meter Adjust Value
Analog Output
Load Torque 150%