HX7+ ASD Installation and Operation Manual 83
Input Terminal Priority
Program Terminal Selection Input Special
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Terminal Board even though
the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Terminal Board will receive priority over
commands from the keypad.
See for further information on using the Jog function.
See F250F252 for further information on DC Injection Braking.
Settings:
0 — Enabled (box checked)
1 — Disabled
Direct Access Number — F106
Parameter Type — Check Box
Factory Default Disabled
Changeable During Run — No
Extended Terminal Function
Program Terminal Selection Input Special
The Extended Terminal Function is used with the optional ASD-Multicom
card only. This parameter defines the format of the binary or BCD data when
using the option card.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Reverse 12-Bit Binary
6 — Reverse 16-Bit Binary
7 — Reverse 3-Digit BCD
8 — Reverse 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the Terminal Board as binary bits 0 – 3 (
F115F118). The
Frequency Mode #1 Selection (F004) must be set to Use Binary/BCD Input.
For proper scaling of the binary or BCD input, parameters F228F231 must be
configured [BIN Reference Point #1, BIN Reference #1 (frequency), Bin
Reference Point #2, and BIN Reference #2 (frequency)].
Direct Access Number — F107
Parameter Type — Selection List
Factory Default None
Changeable During Run — No
F106 F107