21
Example Table Excerpt:
Register Bit Function Bank Mask Adjustment Range Multiplier
01
word
Frequency command DPRAM FFFF 0.00 400.00Hz
Actual frequency will be
limited by LL, UL and Fmax.
0.01
02 0 RUN command DPRAM 0: Stop
1: Run
1 STOP Command (has priority
over RUN command)
0: run enabled
1: stop
2 Forward reverse run
selection
0: reverse
1: forward
Other Programming Register Notes:
Throughout this document, the abbreviations "LL", "UL", and "Fmax" will stand for
LOWER LIMIT FREQUENCY, UPPER LIMIT FREQUENCY, and MAXIMUM
OUTPUT FREQUENCY, respectively.
Reading from registers, register areas or coils marked as "Reserved" will return
data values of 0. Writing to registers, register areas or coils marked as
"Reserved" will have no effect. In both of these cases, as these actions are not
considered errors, no exception response will be generated.
Certain holding registers cannot be written to while the inverter is running. These
registers will be indicated by the character (T). If an attempt is made to write to
these registers while the inverter is running, an exception response will be
generated.
The holding register data for all read/write registers with Bank information listed as
0/1 will be retrieved from bank 0 (RAM) during reads and will be written to both
banks 0 and 1 (RAM and EEPROM) during writes.
All parameters in GROUP:COMMUNICATION SETTING PARAMETERS (section
9.3.10) are retrieved from non-volatile memory upon inverter initialization. When
any of these registers are modified, therefore, the inverter must be reset for the
changed values to take effect.