28
9.3.2 GROUP:FUNDAMENTAL PARAMETERS #2
Register Function / Title Bank Mask Adjustment Range Multiplier
34 BASE FREQUENCY #2 0 / 1 FFFF 09C4 9C40 (25.00 400.00) 0.01
35 MAXIMUM OUTPUT
VOLTAGE #2
0 / 1 FFFF 0000 0258 (0 600) 1
36 VOLTAGE BOOST #2 0 / 1 FFFF 0000 012C (0.0 30.0) 0.1
37 ELECTRONIC THERMAL
PROTECT LVL #2
0 / 1 00FF 000A 0064 (10 100) 1
38 STALL PROTECTION
SELECTION #2
0 / 1 0040 0000: ON (0)
0040: OFF (1)
39 0 STALL PROTECTION
LEVEL #2
0 / 1 00FF 000A 00D7 (10 215) 1
3A ACCELERATION TIME
#2
0 / 1 FFFF 0001 EA60 (0.1~ 6000.0)
0001 EA60 (0.01~ 600.00)
0.1
0.01
3B DECELERATION TIME
#2
0 / 1 FFFF 0001 EA60 (0.1~ 6000.0)
0001 EA60 (0.01~ 600.00)
0.1
0.01
3C ACC/DEC PATTERN #2
SELECTION
0 / 1 0030 0000: Linear (0)
0010: Self-adjusting (1)
0020: S-Pattern #1 (2)
0030: S-Pattern #2 (3)
3D ACC/DEC #1/#2
SWITCH FREQUENCY
0 / 1 FFFF 0000 Fmax 0.01
9.3.3 GROUP:PANEL CONTROL PARAMETERS
Register Function / Title Bank Mask Adjustment Range Multiplier
3E DIRECTION SELECTION
(FORWARD/REV)
0 / 1 0004 0000: Reverse (0)
0004: Forward (1)
3F STOP PATTERN
SELECTION
0 / 1 0040 0000: Decelerated stop (0)
0040: Coast stop (1)
40 FUNDAMENTAL PARAM
SWITCHING
0 / 1 0004 0000: V/F #1 (1)
0004: V/F #2 (2)
41 ACCEL/DECEL #1/#2
SELECTION
0 / 1 0008 0000: Acc / dec #1 (1)
0008: Acc / dec #2 (2)
42 PANEL RESET
SELECTION
0 / 1 0030 0000: All possible (0)
0010: OL only (1)
0020: OL, OC only (2)
43 PANEL FEEDBACK
CONTROL
0 / 1 0001 0000: Feedback valid (0)
0001: Feedback invalid (1)