9.2 Read-Only Registers
Register Bit Function Bank Mask Adjustment Range Multiplier
05
word
Output frequency monitor DPRAM FFFF 0.00 ~ 400.00Hz 0.01
06 0 Run • stop status DPRAM 0: Stopped
1: Running
1 Run enable 0: Run enabled
1: Stopped
2 Forward • reverse status 0: Reverse
1: Forward
3 Acc / dec #1 / #2 selection
status
0: Acc / dec #1
1: Acc / dec #2
4 Reserved
5 Fault status 0: Faulted
1: Not Faulted
6 Reserved
7 Jog mode status 0: Normal (acc/dec mode)
1: Jog mode
8 Feedback enable status 0: Feedback invalid
1: Feedback valid
9 Compulsory DC injection
braking mode
0: DC inject. braking inactive
1: DC inject. braking active
A Fundamental parameter
switching
0: V/F #1
1: V/F #2
B Coast stop command status 0: Normal
1: Coast to stop
C Emergency off command 0: Normal
1: Emergency off
D Reserved
E Main Circuit Undervoltage 0: Normal
1: Undervoltage
F Reserved
07
word
Output current monitor DPRAM 00FF 0 ~ 255% 1
08
word
Output voltage monitor
(Note 1)
DPRAM FFFF 0 ~ 232% 0.1
09
word
IV terminal analog input
value
0 FFFF 0000 ~ FFFF (0% ~ 100%) 1
0A
word
RX terminal analog input
value
0 FFFF 0000 ~ 7FFF (-100% ~ 0%)
7FFF ~ FFFF (0% ~ 100%)
1
0B
word
Frequency command monitor
0 FFFF 0 ~ 255% 0.1
0D
word
Input terminal status monitor 0 FFFF Refer to Table 1 (page 25)
0E low
byte
Output terminal status
monitor
0 00FF Refer to Table 2 (page 25)
high
byte
Inverter Status 2 FF00
0F
word
Inverter Status 1 0 FFFF Refer to Table 3 (page 26)
10
word
Present trip 0 00FF
11 high
byte
4th Past trip (most recent) 0 7F00
low
byte
3rd past trip 007F Refer to section 9.6 for fault
codes
12 high
byte
2nd past trip 0 7F00
low
byte
1st past trip (oldest) 007F
13
word
Pre-compensation output
frequency
0 FFFF 0000 ∼ 9C40
(0.00 ∼ 400.00 Hz)
0.01