EasyManua.ls Logo

Toshiba TOSVERT-130 G3 - Page 25

Toshiba TOSVERT-130 G3
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Register Bit Function Bank Mask Adjustment Range Multiplier
14
word
Post-compensation output
frequency
0 FFFF 0000 9C40
(0.00 400.00 Hz)
0.01
15
word
Torque current monitor 0 FFFF (Note 2) 0.01
16 low
byte
Excitation current monitor 0 00FF 00 FF (0 ~ 255%) 1
high
byte
Reserved
17
word
PID feedback value 0 FFFF (Note 2) 0.02
18
word
Motor overload ratio 0 FFFF 0 ~ 65535 100/65535
19
word
Inverter overload ratio 0 FFFF 0 ~ 65535 100/65535
1A
word
DBR overload ratio 0 FFFF 0 ~ 65535 100/65535
1B
word
Input power (%) 0 FFFF 0 ~ 6553.5 0.1
1C
word
Input power (kW) 0 FFFF (Note 3)
1D
word
Output power (%) 0 FFFF (Note 2) 0.1
1E
word
Output power (kW) 0 FFFF (Note 2, Note 3)
1F
word
RR input 0 FFFF 0 ~ 65535 100/65535
20
word
CPU version number 2 FFFF
21
word
External ROM version
number
3 FFFF
22
word
EEPROM version number 1 FFFF
23 low
byte
Inverter typeform monitor 0 00FF Refer to Table 4 (page 26)
8 Input / output power units 0 0100 0: 0.01kW
1: 0.1kW
9,A Command mode status 0 0600 00: terminal
01: panel
10: option
11: RS232C
B,C Frequency mode selection
status
0 1800 00: terminal
01: panel
10: option
11: RS232C
D,E,
F
Reserved
24 low
byte
Modbus Interface card
software revision
high
byte
Modbus Interface card
software version
25
word
Output current (amps) FFFF 0.0 ~ 6553.5 A 0.1
(Note 1) These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in
GROUP:UTILITY PARAMETERS; they are always in units of %.
(Note 2) These registers use signed data (data values larger than 7FFFH are negative). If the register data is
8000H or larger, the actual value can be obtained by: actual value = - [FFFFH - (register data) + 1].
(Note 3) If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier is
0.1. These values are automatically set according to the inverter’s capacity.
efesotomasyon.com -Toshiba inverter,drive,servo,plc

Related product manuals