27
9.3 Read/Write Registers
9.3.1 GROUP:FUNDAMENTAL PARAMETERS #1
Register Function / Title Bank Mask Adjustment Range Multiplier
26 MAXIMUM OUTPUT
FREQUENCY (T)
0 / 1 FFFF 0BB8 9C40 (30.00400.00) 0.01
27 BASE FREQUENCY #1 0 / 1 FFFF 09C4 9C40 (25.00400.00) 0.01
28 BASE FREQUENCY
VOLTAGE SELECT (T)
0 / 1 0030 0000: Input voltage level (0)
0020: Automatic setting (1)
0030: Stationary setting (2)
29 MAXIMUM OUTPUT
VOLTAGE #1
0 / 1 FFFF 0000 0258 (0 600) 1
2A REVERSE OPERATION
DISABLE SELECT
0 / 1 0020 0000: Reverse allowed (0)
0020: Reverse not allowed (1)
2B UPPER LIMIT
FREQUENCY
0 / 1 FFFF 0000 ~ Fmax 0.01
2C LOWER LIMIT
FREQUENCY
0 / 1 FFFF 0000 UL, Fmax 0.01
2D VOLTS PER HERTZ
PATTERN (T)
0 / 1 000F 0000: Constant torque (1)
0001: Variable torque (2)
0002: Auto. torque boost (3)
0006: #3 w/ auto. energy savings (4)
000A: Vector control (5)
000E: #5 w/ auto. energy savings (6)
2E 1, 2
VOLTAGE BOOST
#1
0 / 1 FFFF 0000 012C (0.0 30.0) 0.1
2F ACCELERATION TIME
#1
0 / 1 FFFF 0001 EA60 (0.01~ 600.00)
0001 EA60 (0.1~ 6000.0)
0.01
0.1
30 DECELERATION TIME
#1
0 / 1 FFFF 0001 EA60 (0.01~ 600.00)
0001 EA60 (0.1~ 6000.0)
0.01
0.1
31 ACC/DEC PATTERN #1
SELECTION
0 / 1 0030 0000: Linear (0)
0010: Self-adjusting (1)
0020: S-Pattern #1 (2)
0030: S-Pattern #2 (3)
32 ACCEL/DECEL PATTERN
ADJUST LOW
0 / 1 00FF 0003 ~ 00FD (0 50) (Note 1)
1
33 ACCEL/DECEL PATTERN
ADJUST HIGH
0 / 1 00FF 0003 ~ 00FD (0 50) (Note 1)
1
Note 1: Register data = (desired setting x 5 + 3), converted to hexadecimal