[11] Preset speed operation frequency (8~15) [2/2] Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
0293 Preset speed operation frequency 14 ~ Hz 0.1/0.01 0.0 Enabled ●/● ● ● 5. 12
0294
Preset speed operation frequency 15
(Forced operation frequency)
~ Hz 0.1/0.01 0.0 Enabled ●/● ● ● 5. 12
0295 Bumpless operation selection
1:Disabled
2:Enabled
1/1 0 Enabled ●/● ● ● 6. 14
[12] Tripless intensification setup [1/2] Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
0300 PWM carrier frequency 1.0~16.0kHz (2.5~8.0kHz) *1 0.1/0.1 *2 Enabled ●/● ● ● 5. 17
0301 Auto-restart control selection
0:Disabled
1:At auto-restart
2:When turning ST operation standby signal on or
off
3:1+2, 4:Starting
1/1 0 Disabled ●/● ● ● 5. 18. 1
0302 Regenerative power ride-through control
0:Disabled
1:Power ride-through
2:Deceleration stop during power failure
1/1 0 Disabled ●/● ● ● 5. 18. 2
0303 Retry selection 0:Deselect, 1-10 times 1/1 0 Enabled ●/● ● ● 6. 15. 1
0304 Dynamic braking selection
0:Disabled
1:Enabled (braking resistance overload detect)
2:Enabled (braking resistance overload not detect)
1/1 0 Disabled ●/● ● ● 5. 19
0305 Overvoltage limit operation
0:Enabled
1:Disabled
2:Enabled (quick deceleration)
3:Enabled (dynamic quick deceleration)
1/1 2 Disabled ●/● ● ● 6. 15. 2