K-10
E6581386
11
[9] Jogging operation Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
 0260 Jog run frequency ~20.0Hz 0.1/0.01 5.0 Enabled / 6. 10
 0261 Jog run stop pattern
0:Deceleration stop
1:Coast stop
2:DC braking stop
1/1 0 Disabled / 6. 10
 0262 Operation panel jog run mode
0:Disabled
1:Operation panel jog run mode enabled
1/1 0 Enabled / 6. 10
 0264
Input from external contacts - UP response
time
0.0~10.0 sec. 0.1/0.1 0.1 Enabled / 6. 11
 0265
Input from external contacts - UP frequency
step
0.0~ Hz 0.1/0.01 0.1 Enabled / 6. 11
 0266
Input from external contacts - DOWN
response time
0.0~10.0 sec. 0.1/0.1 0.1 Enabled / 6. 11
 0267
Input from external contacts - DOWN
frequency step
0.0~ Hz 0.1/0.01 0.1 Enabled / 6. 11
 0268 Initial UP/DOWN frequency ~ Hz 0.1/0.01 0.0 Enabled / 6. 11
 0269 Initial up/down frequency rewriting
0:Not changed
1:Setting of  changed when power is
turned off
1/1 1 Enabled / 6. 11
[10] Jump frequency Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
 0270 Jump frequency 1 0.0~ Hz 0.1/0.01 0.0 Enabled / 6. 12
 0271 Jumping width 1 0.0~30.0Hz 0.1/0.01 0.0 Enabled / 6. 12
 0272 Jump frequency 2 0.0~ Hz 0.1/0.01 0.0 Enabled / 6. 12
 0273 Jumping width 2 0.0~30.0Hz 0.1/0.01 0.0 Enabled / 6. 12
 0274 Jump frequency 3 0.0~ Hz 0.1/0.01 0.0 Enabled / 6. 12
 0275 Jumping width 3 0.0~30.0Hz 0.1/0.01 0.0 Enabled / 6. 12
[11] Preset speed operation frequency (8~15) [1/2] Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
 0287 Preset speed operation frequency 8 ~ Hz 0.1/0.01 0.0 Enabled / 5. 12
 0288 Preset speed operation frequency 9 ~ Hz 0.1/0.01 0.0 Enabled / 5. 12
 0289 Preset speed operation frequency 10 ~ Hz 0.1/0.01 0.0 Enabled / 5. 12
 0290 Preset speed operation frequency 11 ~ Hz 0.1/0.01 0.0 Enabled / 5. 12
 0291 Preset speed operation frequency 12 ~ Hz 0.1/0.01 0.0 Enabled / 5. 12
 0292 Preset speed operation frequency 13 ~ Hz 0.1/0.01 0.0 Enabled / 5. 12

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals