E6581386
F-1
6
6. Extended parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes.
⇒ Refer to Section 11, Table of parameters.
6.1 Input/output parameters
6.1.1 Low-speed signal
  : Low-speed signal output frequency
[Parameter setting]
Title Function Adjustment range Default setting
 Low-speed signal output frequency ~ Hz 
Output frequency [Hz]
Time [s]
Low-speed signal output
P24-OUT1 terminals (Default setting)
P24-OUT2 terminals
FLA-FLB-FLC terminals
ON
OFF
Low-speed signal output: Inverted
ON
OFF
0
Set frequency
[Connection diagram (Sink logic)]
P24
OUT1 (or OUT2)
NO
CC
Ry
•Function
When the output frequency exceeds the setting of  an ON signal will be generated. This signal can be
used as an electromagnetic brake excitation/release signal.
+Through the open collector terminal OUT1 or OUT2 (24Vdc-50mA [max.]).
• Output terminal setting
The low-speed signal (ON signal) output function has been assigned to the terminal OUT1 by default. This
setting must be changed to invert the polarity of the signal.
[Parameter setting]
Title Function Adjustment range Example of setting
Output terminal function selection
1(OUT1)
~
(ON signal) or
(OFF signal)
Note:To put out signals to OUT2, select the parameter .