E6581386
F-22
6
[Parameter setting]
Title Function Adjustment range Default setting
Jump frequency 1 ~ Hz
Jumping width 1 ~ Hz
Jump frequency 2 ~ Hz
Jumping width 2 ~ Hz
Jump frequency 3 ~ Hz
Jumping width 3 ~ Hz
+If the upper limit frequency () is within jump frequency range,
it is limited to the lowest frequency in the jump frequency range.
+If the lower limit frequency () is within jump frequency range,
it is limited to the highest frequency in the jump frequency range.
+Do not overlap upper limit frequency () and lower limit frequency ()
within jump frequency range.
If they are overlapped, it is operated lowest jump frequency.
+Do not overlap two or more jump frequency ranges, or
it cannot be operated within normal range.
+During acceleration or deceleration,
the jumping function is disabled for the operation frequency.
6.13 Preset speed operation frequencies
6.13.1 Preset speed operation frequency 8 to 15
~ : Preset speed operation frequencies 8 to 15
⇒ For details, refer to Section 5.12.
6.13.2 Forced operation control
: Preset speed operation frequency 15 (Forced operation frequency)
⇒ For details, refer to Section 6.27.
Jumping width 2
Jumping width 1