F-53
6
6.26.15 VI/II analog input wire breakage detection level
 : VI/II analog input wire breakage detection level

: Action in the event of VI/II analog input wire breakage
Function
The inverter will trip if the VI/II value remains below the specified value for 0.3 seconds or moreThe
message “” is displayed.
=: Disabled
・・・・・ The detection function is disabled.
=~
・・・・・・・・ If the VI/VII input value remains below the specified value for 0.3 seconds or more, the
inverter will act in accordance with the setting of .
Title Function Adjustment range Default setting

VI/II analog input wire breakage
detection level
:None
~ %

Action in the event of VI/II analog
input wire breakage
: Trip mode
: The inverter operates the motor at
preset speed operation frequency 14.
Note: Depending on the degree of deviation of the analog data detected, a wire breakage may be detected within a
period shorter than the specified one.
6.26.16 Guide to time of replacement
 : Annual average ambient temperature
Function
You can set the inverter so that it will calculate the remaining useful life of the cooling fan, main circuit
capacitor and on-board capacitor from the ON time of the inverter, the operating time of the motor, the
output current (load factor) and the setting of  and that it will display and send out an alarm through
output terminals when each component is approaching the end of its useful life.
Title Function Adjustment range Default setting
 Annual average ambient temperature
: -10~+10°C
: +11~+20°C
: +21~+30°C
: +31~+40°C
: +41~+50°C
: +51~+60°C
Note 1: Using , enter the annual average temperature around the inverter. Be careful not to enter the annual
highest temperature.
Note 2: Set  at the time of installation of the inverter, and do not change its setting after the start of use.
Changing the setting may cause a part replacement alarm calculation error.