E6581386
M-1
13
13. 
Before making a service call
 - Trip information and remedies
13.1 Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table,
contact your supplier.
[Trip information]
Error
code
Description Possible causes Remedies
*
Overcurrent
during
acceleration
•
The acceleration time 
is too short.
•The V/f setting is improper.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•A special motor (e.g. motor with a
small impedance) is used.
•
Manual torque boost value 
 is lar
e.
•Increase the acceleration time .
•Check the V/f parameter setting.
•Use (Auto-restart) and  (Regenerative
power ride-though control).
•Increase the carrier frequency .
•Decrease  setting value.
•Decrease 
stall prevention level
 to 130 as
a guide.
•Increase  (carrier frequency) setting value if it
is set at lower value (2kHz or less).
*
Overcurrent
during
deceleration
•The deceleration time  is too
short. (in deceleration)
•Increase the deceleration time .
*
Overcurrent
during fixed
speed
•The load fluctuates abruptly.
•The load is in an abnormal
condition.
•Reduce the load fluctuation.
•Check the load (operated machine).
[Note] , ,
 originate from
causes other than those
mentioned above.
•
A main circuit elements is defective.
•Overheat protection is activated.
•Make a service call.
•Check operation of cooling fan.
•Check cooling fan control mode parameter
.
*
U-phase 
arm
short-circuit
•A main circuit elements is defective
(U-phase).
•Make a service call.
*
V-phase 
arm
short-circuit
•A main circuit elements is defective
(V-phase).
•Make a service call.
*
W-phase 
arm
short-circuit
•A main circuit elements is defective
(W-phase).
•Make a service call.
Loaded side
overcurrent at
start time
•The insulation of the output main
circuit or motor is defective.
•The motor has too small
impedance.
•The drive circuit board in the
inverter was damaged.
•Check the cables and wires for defective
insulation.
•Selection of short circuit detection at starting
parameter .
•If this error message appears when a motor is not
connected to the inverter, the inverter itself ma
 be
faulty, so make a service call.
D
namic brakin
element
overcurrent
(200V-55kW or
larger, 400V-
90kW or lar
er
•PB-PC/+ circuit is shorted.
•A resistor with resistance smaller
than the minimum allowable
resistance is connected.
•Parameter  was set to  or 
without connecting regenerative
brake or with wire disconnected
(with dynamic braking).
•Check the impedance wirin
 for the resistor, etc.
•Make a service call.
•Check if regenerative brake is connected.
•If regenerative brake is not necessary, set
parameter  to .
 Overheating
•The cooling fan does not rotate.
•The ambient temperature is too
high.
•The vent is blocked up.
•A heat generating device is
installed close to the inverter.
•The thermistor in the unit is
disconnected.
•Restart the operation b
 resettin
 the inverter afte
it has cooled down enough.
•The fan requires replacement if it does not rotate
during operation.
•Secure sufficient space around the inverter.
•Do not place any heat generating device near the
inverter.
•Make a service call.
Thermal trip
stop command
from external
device
•An input signal is impressed at
control input terminal PTG for
optional add-on cards.
•A thermal trip command (input
terminal function:  or ) is
issued by an external control
device.
•The motor is overheated, so check whether the
current flowing into the motor exceeds the rated
current.
* In the event one of the error codes  to  and  to  appears, in which case a main circuit
component has most probably failed, the only way to reset the inverter is to turn power off and back on.
(Continued overleaf)