EasyManua.ls Logo

Toshiba VF-PS1 - Control Mode for Low Current

Toshiba VF-PS1
307 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581386
F-49
6
6.26.7 Control mode for low current
 : Low current detection hysteresis width

: Low current trip selection

: Low current detection current

: Low current detection time
Function
If the current is lower than  level and passes for a time longer than , the inverter trips.
Trip information is displayed as “.”
=: No tripping (Failure signal FL deactivated).
A low current alarm can be put out by setting the output terminal function selection parameter.
=: The inverter will trip (the failure signal FL will be activated) if a current below the current set with
 flows for the period of time specified with .
Title Function Adjustment range Default setting
 Low current detection hysteresis width ~ % 
 Low current trip selection
: No trip
:Trip
 Low current detection current ~ %
 Low current detection time ~ sec.
<Example of operation>
Output terminal function: 26 (UC) Low current detection
= (No trip)
Ex.) When outputting low current detection signals through output terminal OUT1
Title Function Adjustment range Example of setting
 Output terminal function selection 1(OUT1) ~ 
Note:To put out signals to the terminal OUT2, select the parameter .
Time [sec]
 + 

Output current [%]
Low current
signal output

ON
OFF
OFF
less than

+When = (tripping), the inverter will trip if low current lasts for the period of time set with .
After tripping, the low current signal remains ON.

Table of Contents

Related product manuals