5.18.2 Regenerative power ride-through control/Deceleration stop during power
failure
: Regenerative power ride-through control
: Non-stop control time/Deceleration time during power failure
[Parameter setting]
Title Function Adjustment range Default setting
Regenerative power ride-through
control selection
:Disabled
:Power ride-through
:Deceleration stop during power failure:
Non-stop control time/Deceleration
time during power failure
~ sec.
Note 1: The power ride-through control time when = depends on the setting of , and the deceleration
time when = depends on the setting of .
Note 2: Even if these functions are used, a motor may coast according to load conditions.
In this case, use the auto-restart function along with this parameter function.
Note 4: Although the setting of can be written when is set to (non-stop control), it cannot be written
when is set to (momentary power failure slowdown stop).
Q An example of setting when =
[When power is interrupted]
Motor speed
Several hundreds of milliseconds
to several tens of seconds.
Input voltage
Coasting time
Note: If power is interrupted
during deceleration stop,
power ride-through control
will not be performed.
[If momentary power failure occurs]
Motor s
eed
Input voltage
Non-sto
control Normal acceleration
•Function
1) Regenerative power ride-through control: When momentary power failure occurs during operation, this
function makes operation continue using the regeneration
energy from a motor.
2) Deceleration stop during power failure: When momentary power failure occurs during operation, this
function stops the motor quickly compulsorily. A forcible stop is
carried out in (Deceleration time) using the regeneration
energy from the motor.
(Deceleration time varies with control.)
After the forced stop, the inverter remains static until you put off
the operation command momentarily.
+The time for which the operation of the motor
can be continued depends on the machine
inertia and load conditions. Before using this
function, therefore, perform verification tests.
+Use with the retry function allows the motor to
be restarted automatically without being
brought to an abnormal stop.