E6581386
E-2
5
5.2 Setting acceleration/deceleration time
 : Automatic acceleration/deceleration

: Acceleration time 1

: Deceleration time 1
5.2.1 Automatic acceleration/deceleration
This automatically adjusts acceleration and deceleration time in line with load size.
 =
* Adjusts the acceleration/deceleration time automatically within the range of 1/8 to 8 times as long as the time
set with the  or , depending on the current rating of the inverter.
 =
* Automatically adjusts speed during acceleration only. During deceleration, speed is not adjusted
automatically but reduced at the rate set with .
DecelerationAcceleration

When load is small
Time [s]
0
DecelerationAcceleration

When load is large
Output
frequency [Hz]
Output
frequency [Hz]
Time [s]
0
Acceleration/deceleration time
decrease Acceleration/deceleration time
increase
Set  (automatic acceleration/deceleration) to or .
[Parameter setting]
Title Function Adjustment range Default setting
 Automatic acceleration/deceleration
:Disabled (Manual setting)
:Automatic setting
:Automatic setting (during
acceleration only)
+ When automatically setting acceleration/deceleration time, always change the acceleration/deceleration time so that
it conforms with the load.
The acceleration/deceleration time changes constantly with load fluctuations.
For inverters that requires a fixed acceleration/deceleration time, use the manual settings (, ).
+ When using a braking resistor or braking unit, do not set the =. Or the regenerative braking resistor may be
overloaded.
+ Use this parameter after actually connecting the motor.
+ Setting acceleration/deceleration time (, ) in conformance with mean load allows optimum setting that
conforms to further changes in load.
+ When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or
deceleration time in time, and therefore may be tripped.
•Function
1) For acceleration time 1  programs the time that it takes for the inverter output frequency to go from
0Hz to maximum frequency .
2) For deceleration time 1  programs the time that it takes for the inverter output frequency to got from
maximum frequency  to 0Hz.