E6581386
M-2
13
(Continued)
Error
code
Description Possible causes Remedies
Inverter
overload
•Rapid acceleration is operated.
•The DC braking amount is too
large.
•The V/f setting is improper.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•The load is too large.
•Increase the acceleration time .
•Reduce the DC braking amount  and the
DC braking time .
•Check the V/f parameter setting.
•Use  (Auto-restart) and  (Regenerative
power ride-though control).
•Use an inverter with a larger rating.
 Motor overload
•
The V/f parameter is improperl
 set.
•The motor is locked up.
•Low-speed operation is performed
continuously.
•An excessive load is applied to the
motor during operation.
•Check the V/f parameter setting.
•Check the load (operated machine).
•Check the  setting and adjust 
according to the sustainable overload in the motor
low-speed range.
• Reduce the DC braking amount  and the
DC braking time .
Dynamic
braking resistor
overload
•Rapid deceleration is operated.
•Dynamic braking is too large.
•Increase the deceleration time .
•Increase the capacity of dynamic braking resistor
(wattage) and adjust PBR capacity parameter
.
Overvoltage
during
acceleration
•
The input volta
e fluctuates abnormall
.
1
The power suppl
 has a capacit
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•Insert a suitable input reactor.
•Use  (Auto-restart) and  (Regenerative
power ride-though control).
Overvoltage
during
deceleration
•
The deceleration time 
 is too
short (regenerative energy is too
large).
•The d
namic brakin
 resistor has a
considerably large resistance.
•
 
D
namic brakin
 resistor
 is OF
.
Overvolta
e limit operation 
is OFF.
•
The input volta
e fluctuates abnormall
.
1
The power suppl
 has a capacit
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•Increase the deceleration time .
•Install a dynamic braking resistor.
•Decrease dynamic braking resistance. (Also reset
the .)
•Set dynamic braking mode parameter 
properly.
•Set overvolta
e limit operation  properl
.
•Insert a suitable input reactor.
Overvoltage
during fixed
speed operation
•The input voltage fluctuates
abnormally.
1
The power suppl
 has a capacit
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•The motor is in a regenerative
state because the load causes the
motor to run at a frequency higher
than the inverter output frequenc
.
•Insert a suitable input reactor.
•Install a dynamic braking resistor.
* Overtorque
•Overtorque reaches to a detection
level during operation.
•Check system error.
•Check whether the motor is overloaded or the
brake is engaged.
*
Low current
operation
•The output current decreased to a
low-current detection level during
operation.
•Check the suitable detection level for the system
().
•Make a service call if the setting is correct.
*
Undervoltage
(main circuit)
•The input voltage (in the main
circuit) is too low.
•Check the input voltage.
 Emer
enc
 stop
•Inverter is stopped by panel
operation during automatic or
remote operation.
•A stop command (input terminal
function:  or ) is issued by
an external control device.
•Reset the inverter.
  *Presence or absence of parameter trip can be selected.
(Continued overleaf)