Loading...
CG-SVX17D-EN 179
Diagnostics
Comm Loss: Evaporator Water
Pump 2 Relay
Comm Loss: Evaporator Water
Pump 2 Relay
Comm: Evap Water Pump
Relay
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Evaporator Pump
1 Fault Input
Comm Loss: Evaporator Pump
1 Fault Input
Comm: Evap Pump Fault
Input
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Evaporator Pump
2 Fault Input
Comm Loss: Evaporator Pump
2 Fault Input
Comm: Evap Pump Fault
Input
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Evap Pump
Inverter 1 Run Command
Comm Loss: Evap Pump
Inverter 1 Run Cmd
Comm: Evap Pmp Inv 1 Run
Cmd
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Evap Pump
Inverter 1 Fault Input
Comm Loss: Evap Pump Inv 1
Fault Input
Comm: Evap Pmp Inv 1 Flt
Inp
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Evap Pump
Inverter 1 Frequency Feedback
Comm Loss: Evap Pump Inv 1
Freq Feedback
Comm: Evap Pmp Inv 1 Freq
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Suction
Temperature
Comm Loss: Suction
Temperature
Comm: Suction
Temperature
Circuit Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Heat/Cool Switch
Comm Loss: Heat/Cool Switch
Comm: Heat/Cool Switch
Chiller Normal Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Electronic
Expansion Valve
Comm Loss: Electronic
Expansion Valve
Comm: EXV
Circuit Immediate Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Cooling EXV
Comm Loss: Cooling EXV
Comm: Cooling EXV
Circuit Immediate Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Comm Loss: Heating EXV
Comm Loss: Heating EXV
Comm: Heating EXV
Circuit Immediate Latch All
Continual loss of communication
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote