10
SS-SVN016A-EN
Condenser and Air Handler Pair Wiring Information
Pairing C or 3
Figure 2. Pairing C or 3 Electromechanical condenser with Symbio Air Handler
T-STAT R
T-STAT GND
T-STAT G
T-STAT Y1
Electromechanical Condenser
Symbio Air Handler 2 Speed Fan
THERMOSTAT WIRE
LTB1-B1
LTB1-R
RB-J10-2
RB-J10-1
RB-J5-1
RB-J5-6
CONTROL WIRE
T-StatT-Stat
RELAY BOARD
J5
COIL DEFROST
R (24VAC)
T-STAT GND
T-STAT G
T-STAT Y1
T-STAT Y2
T-STAT W1
T-STAT W2
1 2 3 4 5 6 7 8
J6
1 2 3
O (IN)
OA (OUT)
OB (OUT)
J7
1 2 3
COMMON
MODBUS -
MODBUS +
IMC -
J4
1 2 3 4
IMC +
COMMON
24VAC IN
(RB)
LTB1
B1
B2
Y1
Y2
R
LTB1
B1
B2
Y1
Y2
R
J10
24VAC IN
COMMON
1 2
J10
24VAC IN
COMMON
1 2
J9
INDOOR FAN RUN OUT
COMMON
1 2
J8
24VAC OUT
COIL DEFROST IN
1 2
LTB1-B2
RB-J5-5
R
BK
EDC
T-STAT W2
T-STAT W1
T-STAT Y2
LTB1-Y2
LTB1-Y1
Thermostat Connections
TThheerrmmoossttaatt wwiirree uupp ttoo sseevveenn ccoonndduuccttoorrss
1. Connect a pair of conductors from thermostat R and ground terminals to relay board J10-1
and relay board J5-3. It is recommended to use the J10-1 terminal on the relay board instead
of the J5-2 terminal on the relay board to power the thermostat.
2. Connect the remaining conductors to their corresponding terminal on the J5 connector on the
relay board. Depending on the size and setup of the application, the number of conductors
will vary:
a. The W1 and W2 connections are needed only if the air handler has an electric heat
accessory installed. A new electric heater must be used with a Symbio air handler. Legacy
electric heaters cannot be reused on Symbio air handlers.
b. On units with single compressor, jumper relay board J5-5 and J5-6 together to enable
high speed fan on call for cooling.