SS-SVN016A-EN
7
Condenser and Air Handler Pairings
Table 3. Model number descriptions
TWE Air Handler with Symbio
Digit 15 Controls
1 = Constant Volume
C = 2 Stage Airflow (Electromechanical Condenser Only)
D = 2 Stage Airflow/Single Zone VAV (Symbio Condenser Only)
TWE Air Handler (pre-Symbio)
Digit 15 Controls
0 = Constant Volume
A = 2 Stage Airflow (Electromechanical Condenser Only)
B = Single Zone VAV (ReliaTel Condenser Only)
Table 4. Condenser and air handler pairing instructions
Condenser
(model #
digit)
Air Handler
Wiring
Reference
Instructions
Type
Supply Fan
Type
(model # digit)
Odyssey
Electromechani-
cal
(Digit 15 = E)
Odyssey Symbio
Constant Volume
(Digit 15 = 1)
“Pairing C or
3, p. 10
2-Speed Airflow
(Digit 15 = C)
Single Zone VAV
(Digit 15 = D)
“Pairing D, p.
12
Pairing F, D or G require wire harness kit WIR010190 (required)
and WIR010185 (optional) to connect Air Handler Relay Board
to VFD.
Odyssey ReliaTel
(Digit 15 = R)
Odyssey Symbio
Constant Volume
(Digit 15 = 1)
“Pairing 4, p.
14
2-Speed Airflow
(Digit 15 = C)
“Pairing E, p.
16
Single Zone VAV
(Digit 15 = D)
“Pairing F, p.
16
Pairing F, D or G require wire harness kit WIR010190 (required)
and WIR010185 (optional) to connect Air Handler Relay Board
to VFD.