14
SS-SVN016A-EN
Pairing 4
Figure 4. Pairing 4 for ReliaTel Condenser to Symbio Air Handler Constant Volume
Reliatel Condenser
Symbio Air Handler Constant Volume
THERMOSTAT OR
ZONE SENSOR WIRE
OR
SensorSensor
CONTROL WIRE
T-StatT-Stat
LTB1-R
J10
RELAY BOARD
J5
COIL DEFROST
R (24VAC)
T-STAT GND
T-STAT G
T-STAT Y1
T-STAT Y2
T-STAT W1
T-STAT W2
1 2 3 4 5 6 7 8
J6
1 2 3
O (IN)
OA (OUT)
OB (OUT)
J7
1 2 3
COMMON
MODBUS -
MODBUS +
IMC -
J4
1 2 3 4
IMC +
COMMON
24VAC IN
24VAC IN
COMMON
1 2
(RB)
LTB1
B1
R
CD
H1
H2
EF
RB-J10-2
LTB1-B1
J8
24VAC OUT
COIL DEFROST IN
1 2
RB-J10-1
LTB1-CD
RB-J5-1
RB-J5-7
RB-J5-8
LTB1-H1
LTB1-H2
LTB1-EF
RB-J5-4
W1(R)
R
BK
EDCEDC
R
BK
EDC
J9
INDOOR FAN RUN OUT
COMMON
1 2
Air Handler to Condenser Connections
CCoonnttrrooll WWiirree —— TThheerrmmoossttaatt ssttyyllee wwiirree uupp ttoo ssiixx ccoonndduuccttoorrss
Table 7. Pairing 4 air handler to condenser wiring
Cond. Required /
Optional
Air Handler
Connection
Condenser
Connection
Purpose
Instructions
1 Required RB-J5-4 LTB1-EF Run command for supply fan
2 Optional RB-J10-1 LTB1-R Power relay board It is recommended that the air handler
and condensing unit share low voltage
power. If the air handler and
condensing unit have separate low
voltage power, these conductors can be
omitted, but isolation relays are
needed on the remaining Control Wire
conductors.
3 Optional RB-J10-2 LTB1-B1 Power relay board