30
SS-SVN016A-EN
Pairing Z
Figure 12. Pairing Z for two Symbio Condensers to one Symbio Air Handler
SYMBIO 700
(UC) ONLY FIELD
CONNECTIONS SHOWN
J16
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
R (24VAC OUT)
T-STAT Y1
24VAC OUT
LIMIT/SHED
1 2
Symbio Condensers
Symbio Air Handler Constant 2 Speed
THERMOSTAT OR
ZONE SENSOR WIRE
OR
SensorSensor
CONTROL WIRE
T-StatT-Stat
CONTROL WIRE
G
Relay
O
Relay
Y2
Relay
ADAPTER BOARD
IMC -
J15
1 2 3 4
COMMON
24VAC OUT
IMC +
1 2 3
MODBUS -
MODBUS +
COMMON
J16
J18
INDOOR FAN RUN OUT
COMMON
1 2
INDOOR FAN HI SPD OUT
COMMON
1 2
J17
(AB) ONLY FIELD
CONNECTIONS SHOWN
SYMBIO 700
(UC) ONLY FIELD
CONNECTIONS SHOWN
J16
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
R (24VAC OUT)
T-STAT Y1
24VAC OUT
LIMIT/SHED
1 2
ADAPTER BOARD
IMC -
J15
1 2 3 4
COMMON
24VAC OUT
IMC +
1 2 3
MODBUS -
MODBUS +
COMMON
J16
J18
INDOOR FAN RUN OUT
COMMON
1 2
INDOOR FAN HI SPD OUT
COMMON
1 2
J17
(AB) ONLY FIELD
CONNECTIONS SHOWN
G
O
Y2
Y1
Thermostat
INDOOR FAN RUN
24VAC
Indoor
Fan
Run Relay
D
Relay
GND
GND
EDC
Condenser 1
Condenser 2
R
Air Handler
NNoottee:: This diagram is an example of how to use isolation relays for wiring two Odyssey Symbio
single-compressor condensers.
CCoonnddeennsseerr aanndd AAiirr HHaannddlleerr PPaaiirr WWiirriinngg IInnffoorrmmaattiioonn