SS-SVN016A-EN
29
Pairing Y
Figure 11. Pairing Y for Symbio Condenser to Generic Air Handler
Symbio Condenser
Generic Air Handler Constant Volume
THERMOSTAT OR
ZONE SENSOR WIRE
OR
SensorSensor
INDOOR FAN RUN
EDC
GND
CONTROL WIRE
T-StatT-Stat
ADAPTER BOARD
IMC -
J15
1 2 3 4
COMMON
24VAC OUT
IMC +
1 2 3
MODBUS -
MODBUS +
COMMON
J16
J18
INDOOR FAN RUN OUT
COMMON
1 2
INDOOR FAN HI SPD OUT
COMMON
1 2
J17
(AB) ONLY FIELD
CONNECTIONS SHOWN
24VAC
SYMBIO 700
(UC) ONLY FIELD
CONNECTIONS SHOWN
24VAC OUT
LIMIT/SHED
1 2
24VAC OUT
LIMIT/SHED
1 2
J16
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
R (24VAC OUT)
T-STAT Y1
GND
Air Handler
NNootteess::
• Install supply fan run out, (UC) J18-1, and ground (UC) J18-2 to air handler.
• Power (24VAC) and ground from the condenser are required for Evaporator Defrost Control (EDC) signal.
If the EDC switch in the air handler will be utilized for low evaporator compressor protection, the
Symbio Service and Installation Mobile Application can be used to edit the (EDC) for direct or
reverse logic. Go to Tools > Service > Customer Connection Polarity, and change the Demand
Limit Input to DDiirreecctt or RReevveerrsseedd.
CCoonnddeennsseerr aanndd AAiirr HHaannddlleerr PPaaiirr WWiirriinngg IInnffoorrmmaattiioonn