SS-SVN016A-EN
11
Air Handler to Condenser Connections
CCoonnttrrooll WWiirree —— TThheerrmmoossttaatt ssttyyllee wwiirree uupp ttoo ffiivvee ccoonndduuccttoorrss
Table 5. Pairing C or 3 air handler to condenser wiring
Cond. Required/
Optional
Air Handler
Connection
Condenser
Connection
Purpose
Instructions
1 Required (RB) J10-1 LTB1-R 24VAC If the air handler and condensing units have
separate low voltage power, these conductors
can be omitted, but isolation relays are
needed on the remaining Control Wire
conductors.
2 Required (RB) J10-2 LTB1-B1 Ground
3 Required (RB) J5-5 LTB1-Y1 Compressor 1
4 Optional (RB) J5-6 LTB1-Y2 Compressor 2
5 Optional (RB) J5-1 LTB1-B2 EDC This conductor is optional and is only needed if
compressor protection at low evaporator
temperatures is desired.
Evaporator Defrost Control
TThheerrmmoossttaatt ssttyyllee wwiirree
1. If the EDC switch in the air handler will be utilized for low evaporator compressor protection,
the factory wire landed on relay board J8-1 must be cut and moved to terminal relay board
J10-2.
2. Move wire from terminal “H” to terminal “L” on EDC switch to enable normally closed switch
operation. This step is required.
CCoonnddeennsseerr aanndd AAiirr HHaannddlleerr PPaaiirr WWiirriinngg IInnffoorrmmaattiioonn