a. The W1 and W2 connections are needed only if the air handler has an electric heat
accessory installed. A new electric heater must be used with a Symbio air handler. Legacy
electric heaters cannot be reused on Symbio air handlers.
b. On units with single compressor, jumper relay board J5-5 and J5-6 together to enable
high speed fan on call for cooling.
Air Handler to Condenser Connections
CCoonnttrrooll WWiirree —— TThheerrmmoossttaatt ssttyyllee wwiirree uupp ttoo ffiivvee ccoonndduuccttoorrss
Table 6. Pairing D air handler to condenser wiring
Cond. Required/
Optional
Air Handler
Connection
Condenser
Connection
Purpose
Instructions
1 Required (RB) J10-1 LTB1-R 24VAC
If the air handler and condensing units have
separate low voltage power, these conductors
can be omitted, but isolation relays are
needed on the remaining Control Wire
conductors.
2 Required (RB) J10-2 LTB1-B1 Ground
3 Required (RB) J5-5 LTB1-Y1 Compressor 1
4 Optional (RB) J5-6 LTB1-Y2 Compressor 2
5 Optional (RB) J5-1 LTB1-B2 EDC
If the EDC switch in the air handler will be
utilized for low evaporator compressor
protection, the factory wire landed on relay
board J8-1 must be cut and moved to terminal
relay board J10-2. The EDC must also be
changed from a normally open to normally
closed switch by moving wire from terminal
“H” to terminal “L” on EDC switch.
Air Handler Connections
TTRR115500 WWiirree –– WWIIRR001100119900 aanndd WWIIRR001100118855 hhaarrnneesssseess
1. Remove the existing wire harness from relay board P1 and VFD terminals 61, 68 and 69. This
harness is not used for this pairing.
2. Connect wiring harness WIR010190 and WIR010185 from relay board J11 to VFD terminals 12,
18, 50, and 53. Verify that jumper exists between VFD terminals 12 and 27.
3. Update the following parameters in the TR150 VFD.
a. Change 3-15 from [11] Local Bus reference to [1] Analog Input 53
b. Change 5-10 from [0] No Operation to [8] Start
c. Change 5-12 from [0] No Operation to [2] Coast Inverse
d. Change 8-01 from [2] Control Word Only to [0] Digital and Control Word
e. Change 8-02 from [1] FC Port to [0] None
f. Verify 4-12 is set to 25 HZ
g. Verify 4-14 is set to 60 HZ
h. Verify 6-10 is set to 0.07V
i. Verify 6-11 is set to 10.00V
j. Verify 6-14 is set to 25 HZ
k. Verify 6-15 is set to 60 HZ