Thermostat and Zone Sensor Wiring
Figure 1. Thermostat or zone senor wiring to Symbio 700 unit controller
Symbio 700
Unit Controller
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
R G W2 Y2 X2 T CCM
R (24VAC OUT)
ZONE TEMPERATURE
COMMON
COOLING SET POINT
UNIT MODE
HEATING SET POINT
COMMON
24 AVC OUT
24 AVC OUT
LOCAL OCCUPANCY
UC-P21
UC-P20
UC-P19
UC-J18
UC-J17
J17
J18
J19
J20 J21
T-STAT Y1
T-STAT W1/0
T-STAT G/VAV CHANGEOVER
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
T-STAT GND
THERMOSTAT
OPTIONAL REMOTE SENSOR
BUILDING
AUTOMATION
COMMUNICATING
ZONE SENSOR
7
7
6
6
5
5
4
4
3
3
2
2
1
1
1 2 3 4 5 10 11
1 2 3 4
ZONE SENSOR
S1 S2
2
2
1
1
24 AVC OUT
BACNET IN+
BACNET IN-
BACNET OUT+
BACNET OUT-
EMERGENCY STOP
2
2
1
1
4
4
3
3
2
2
1
1
Y1/W1/0
Connect a thermostat or other zone control device to the Symbio 700 Unit Controller. Figure 1, p.
9provides wiring guidance for zone sensor BAYSENS135.
NNootteess::
• Symbio controls do not support BAYSENS109 and BAYSENS110 sensor LED
indicators.
• Symbio 700, J21-1 (R), is current limited. Alternately, thermostat 24VAC power can be
connected at Adapter Board (AB) J15-1.