8
SS-SVN016A-EN
Table 4. Condenser and air handler pairing instructions (continued)
Condenser
(model #
digit)
Air Handler
Wiring
Reference
Instructions
Type
Supply Fan
Type
(model # digit)
Odyssey Symbio
(Digit 15 = S)
Odyssey Symbio
Constant Volume
(Digit 15 = 1)
“Pairing A, p.
18
Install a shielded, twisted pair cable if the Air Handler has
Electric Heat and/or requires Single Zone VAV operation (Trane
IMC communication)
2-Speed Airflow
(Digit 15 = C)
“Pairing H, p.
20
Pairing G, H, and 2 will not have heat in defrost.
Pairing G, H, and 2; electric heat will not operate if zone sensor
installed, only with a thermostat
Install a shielded, twisted pair cable if the Air Handler has
Electric Heat and/or requires Single Zone VAV operation (Trane
IMC communication)
Single Zone VAV
(Digit 15 = D)
“Pairing B, p.
18
Install a shielded, twisted pair cable if the Air Handler has
Electric Heat and/or requires Single Zone VAV operation (Trane
IMC communication)
Install a shielded, twisted pair cable for Symbio Condenser
control of the Air Handler supply fan VFD (Modbus
communication)
Odyssey
Electromechanical
Constant Volume
(Digit 15 = 0)
“Pairing 1 or
2, p. 22
Pairing G, H, and 2 will not have heat in defrost.
Pairing G, H, and 2; electric heat will not operate if zone sensor
installed, only with a thermostat.
2-Speed Airflow
(Digit 15 = A)
Odyssey ReliaTel
Variable Speed,
Single Zone VAV
(Digit 15 = B)
“Pairing G
(preferred), p.
24
Pairing G, H, and 2 will not have heat in defrost.
Pairing G, H, and 2; electric heat will not operate if zone sensor
installed, only with a thermostat.
Install a shielded, twisted pair cable for Symbio Condenser
control of the Air Handler supply fan VFD (Modbus
communication)
“Pairing G
(optional), p.
27
Pairing G, H, and 2; electric heat will not operate if zone sensor
installed, only with a thermostat.
Pairing F, D or G require wire harness kit WIR010190 (required)
and WIR010185 (optional) to connect Air Handler Relay Board
to VFD.
This pairing requires the replacement of the RTOM module with
a Symbio Relay Board (MOD03105) and that the VFD wires 81B,
82B, 93B, 94B and 94D be replaced with wire harness kit
WIR010190 (required) and WIR010185 (optional). The Air
Handler will operate as a 2-speed fan.
Generic Air
Handler
Constant Volume
“Pairing Y, p.
29
Two Symbio
Condensers
(2 condensers to
1 air handler)
Odyssey
Electromechanical
“Pairing Z, p.
30
CCoonnddeennsseerr aanndd AAiirr HHaannddlleerr PPaaiirriinnggss