SS-SVN016A-EN
15
Table 7. Pairing 4 air handler to condenser wiring (continued)
Cond. Required /
Optional
Air Handler
Connection
Condenser
Connection
Purpose
Instructions
4 Optional RB-J5-1 LTB1-CD Disable the compressor when EDC
switch activates
If the EDC switch in the air handler will
be utilized for low evaporator
compressor protection, remove the
jumper wire [W1(R)] that is connected
between the terminals LTB1-R & LTB1-
CD in the condenser unit. If EDC is
wired, change the connection from
Terminal ‘H’ (NO) to terminal ‘L (NC).
5 Optional RB-J5-7 LTB1-H1 Command to enable Heat stage1 Conductor is required only if the air
handler is installed with the electric
heat units. If the electric heat kit is
installed, remove the bypass wires 55A
connecting J2-1 & J2-2 on RTRM
(condenser unit) to enable the electric
heat. For 2 stage electric heat, remove
the bypass wire 49A connecting J1-3 &
J1-6 on RTRM (condenser unit).
6 Optional RB-J5-8 LTB1-H2 Command to enable Heat stage2