9 Parameterizing and Configuring
9.1 Parameters
The device has 4 bytes of module parameters, 16 bytes each of IO-Link port parameters and 16
bytes of parameters for VAUX1/VAUX2 monitoring.
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Basic
0x00 - - - - - - - - DXP7_
SRO
- DXP5_
SRO
- DXP3_
SRO
- DXP1_
SRO
-
0x01 - - - - - - - - DXP7_
EN DO
- DXP5_
EN DO
- DXP3_
EN DO
- DXP1_
EN DO
-
IO-Link port 1
0x02 Cycle time GSD Activate
quick
start-up
Data stor-
age mode
Operation mode
0x03 - Mapping
PCDO
Mapping
PDIN
Deactivate
diag.
PDIN
invalid
Rev.
0x04…
0x05
- - - - - - - - -
0x06 Vendor ID (MSB) Vendor ID (LSB)
0x07 Device ID Device ID (LSB)
0x08 Device ID (MSB) Device ID
0x09 - - - - - - - - - - - - - - - -
IO-Link port 2
0x0A…
0x11
Assignment similar to IO-Link port 1 (word 0x02…0x09)
IO-Link port 3
0x12…
0x19
Assignment similar to IO-Link port 1 (word 0x02…0x09)
IO-Link port 4
0x1A…
0x21
Assignment similar to IO-Link port 1 (word 0x02…0x09)
IO-Link port 5
0x22…
0x29
Assignment similar to IO-Link port 1 (Word 0x02...0x09)
IO-Link port 6
0x2A…
0x31
Assignment similar to IO-Link port 1 (Word 0x02...0x09)
IO-Link port 7
0x32…
0x39
Assignment similar to IO-Link port 1 (Word 0x02...0x09)