Operating
Process output data
128
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Name Value Meaning
Module status
[}130]
10.2 Process output data
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Basic
0x00 - - - - - - - - DXP7 - DXP5 - DXP3 - DXP1 -
IO-Link process output data
0x01
…
0x10
IO-Link port 1,
structure depends on the channel parameterization (0…32 byte per channel)
0x11
…
0x20
IO-Link port 2,
structure depends on the channel parameterization (0…32 byte per channel)
0x21
…
0x30
IO-Link port 3,
structure depends on the channel parameterization (0…32 byte per channel)
0x31
…
0x40
IO-Link port 4,
structure depends on the channel parameterization (0…32 byte per channel)
0x41
…
0x50
IO-Link port 5,
structure depends on the channel parameterization (0…32 byte per channel)
0x51
…
0x60
IO-Link port 6,
structure depends on the channel parameterization (0…32 byte per channel)
0x61
…
0x70
IO-Link port 7,
structure depends on the channel parameterization (0…32 byte per channel)
0x71
…
0x80
IO-Link port 8,
structure depends on the channel parameterization (0…32 byte per channel)
VAUX1/VAUX2
0x81 VAUX
2 pin2
C7
(ch15)
VAUX
2 pin2
C6
(ch13)
VAUX
2 pin2
C5
(ch11)
VAUX
2 pin2
C4
(ch9)
- - - - VAUX
1 pin1
C7
(ch14)
VAUX
1 pin1
C6
(ch12)
VAUX
1 pin1
C5
(ch10)
VAUX
1 pin1
C4
(ch8)
VAUX1
pin1
C3
(ch6/7)
VAUX1
pin1
C2
(ch4/5)
VAUX1
pin1
C1
(ch2/3)
VAUX1
pin1
C0
(ch0/1)
Name Value Meaning
I/O data
DXPx DXP output
0 Output inactive
1 Output active, max. output current 2 A
VAUX1 Pin1
Cx (chy/chz)
0 The 24 VDC sensor/actuator supply at Pin1 of the connector is
switched off.
1 The 24 VDC sensor/actuator supply at Pin1 of the connector is
switched on.