Bit Meaning
EVT2 Out-of-specification events
An Out-of-specification event in accordance with the IO-Link specification oc-
curred.
GENERR Common error
The device sends an error (device status 4, in accordance with IO-Link specifica-
tion), which is not clearly specified. Read out the device Event Codes in order to
be able to specify the error more precisely.
HWER Hardware error
General hardware error or device malfunction.
LLVU Lower limit value underrun
The process value lies under the parameterized measurement range or the
chosen measurement range has been chosen too high.
OLV Overload
The connected device detected an overload.
OTMP Overtemperature
A temperature diagnosis is available on the connected device.
PRMERR Parameterization error
The connected device reports a parameterization error (loss of parameters, no
parameter initialization, etc.).
ULVE Upper limit value exceeded
The process value exceeds the parameterized measurement range or the
chosen measurement range has been chosen too low.
VLOW Undervoltage
One of the voltages at the connected device is below the defined range.
VLOW Overvoltage
One of the voltages at the connected device is below the defined range.
10.4.3 PROFINET diagnostics
Module diagnostics
(slot 0 according to configuration tool)
PROFINET Diagnostics
Connector Error code Channel
Undervoltage V1 - 0x0002 0
Undervoltage V2 - 0x0002 1
DXP diagnostics
(slot 1 according to configuration tool)
PROFINET Diagnostics
Channel Connector Error code Channel
Overcurrent output DXP1 C0 0x0001 1
DXP3 C1 0x0001 3
DXP5 C2 0x0001 5
DXP7 C3 0x0001 7
VAUX1/VAUX2 diagnostics
(slot 1, according ot configuration tool)
PROFINET Diagnostics
Error code Channel