Commissioning
Commissioning the device in PROFINET
38
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Acyclic device user data
Index Name Data type Access Comment
Dec. Hex.
1 0x01 Module paramet-
ers
WORD read/
write
Parameter data of the module
(slot 0)
2 0x02 Module designa-
tion
STRING read Designation assigned to the
module (slot 0)
3 0x03 Module revision STRING read Firmware revision of the module
4 0x04 Vendor ID WORD read Ident no. Turck
5 0x05 Module name STRING read The device name assigned to
the module
6 0x06 Module type STRING read Device type of the module
7 0x07 Device ID WORD read Ident no. of the module
8…23 0x08…
0x17
reserved - - -
24 0x18 Module dia-
gnostics
WORD read Diagnostic data of the module
(slot 0).
25…31 0x19…
0x1F
reserved - - -
32 0x20 Input list ARRAY of
BYTE
read List of all module input channels
33 0x21 Output list ARRAY of
BYTE
read List of all module output chan-
nels
34 0x22 Diag. list ARRAY of
BYTE
read List of all I/O-channel dia-
gnostics
35 0x23 Parameter list ARRAY of
BYTE
read List of all I/O-channel paramet-
ers
36…
28671
0x24…
0x6FFF
reserved - - -
28672 0x7000 Module paramet-
ers
WORD read/
write
Activate field bus protocol
28673…
45039
0x7001
…
0xAFEF
reserved - - -
45040 0xAFF0 I&M0-functions read Identification & Maintaining
45041 0xAFF1 I&M0-functions STRING[54] read/
write
I&M Tag function and
location
45042 0xAFF2 I&M2-functions STRING[16] read/
write
I&M Installation Date
45043 0xAFF3 I&M3-functions STRING[54] read/
write
I&M Description Text
45044 0xAFF4 I&M4-functions STRING[54] read/
write
I&M Signature
45045…
45055
0xAFF5
…
0xAFFF
I&M5 to I&M15-
functions
- not supported