Commissioning
Connecting the device to a Siemens PLC in PROFINET
50
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Slot Meaning
VAUX Control Optional mapping of the VAUX diagnositcs into the master's process im-
age.
Module status Optional mapping of the module status into the masters process image.
Configuring IO-Link ports (example)
IO-Link-Port
(Hardware)
Process data
length
IO-Link device GSDML entry
Port 1 2 byte IN Turck temperature
sensor,
TS-530-LI2UPN8X-...
Port-configuration generic:
IN 1 WORD
Port 2 1 Bit IN - DI
Port 3 2 byte IN Turck linearity sensor,
Li100P0-Q25LM0-...
Port-configuration specific:
Li100P0-QU25L
Port 4 2 byte IN
2 byte OUT
Turck I/O hub,
TBIL-M1-16DXP
Port configuration specific:
TBIL-M1-16DXP
Port 5 1 Bit IN - DI
Port 6 1 Bit IN - DI
Port 7 1 Bit IN Turck ultrasonic
sensor,
RU130U-M18E-...
Port-configuration specific:
RU40U-M18E-LiU2PN...(DI)
The IO-Link port is configured as digital
input only.
Port 8 4 byte IN Turck inclinometer,
B2N360-Q42-...,
Port-configuration specific:
B2N360-Q42-E2LiUPN8X2