Commissioning
Connecting the device to a Siemens PLC in PROFINET
52
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Setting IO-Link Port Parameters
In generic port configuration, the ports of the IO-Link master can be operated in IO-Link mode
with different configuration as well as in SIO mode (DI).
In specific port configuration, the IO-Link ports receive the parameters from the GSDML-file.
Parameters like for example Operation mode, Data storage mode, Vendor- and Device ID can-
not be changed.
Select Device view Ò Device overview.
Select the device to be parameterized.
Click Properties ÒGeneral Ò Module parameters.
Set the device parameters.
Fig.42: TIA-Portal – Parametrieren generischer IO-Link-Devices