Commissioning
Commissioning the device in EtherNet/IP™
70
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Device Status
Bit Name Definition
0…1 reserved Default = 0
2 Configured TRUE = 1:
The application of the device has been con-
figured ( default-settings).
3 reserved Default = 0
4…7 Extended Device Status 0011 = no I/O connection established
0110 = at least one I/O connection is in RUN
mode
0111 = at least one I/O connection established,
all in IDLE mode
All other settings = reserved
8 Minor recoverable fault
n Undervoltage
n Force mode of DTM active
n Diagnostics at I/O channel active
9…10 reserved
11 Diag Common error bit
12…15 reserved Default = 0
Common services
Service code Class Instance Service name
Dec. Hex.
1 0x01 yes yes Get_Attribute_All
Returns a predefined list of the object‘s attributes.
5 0x05 No Yes Reset
Starts the reset service for the device.
14 0x0E Yes Yes Get_Attribute_Single
Returns the contents of a specified attribute.
16 0x10 No No Set_Attribute_Single
Modifies a single attribute.