Commissioning
Commissioning the device in EtherNet/IP™
78
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Instance 121 – 4 byte IN/4 byte OUT
The description of the input data can be found in chapter “Operating” [}126]
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status word
0x00 - FCE - - - - V1 - V2 - - - - - - Diag
Inputs
0x01 - DI14
(SIO)
- DI12
(SIO)
- DI10
(SIO)
- DI8
(SIO)
DXP7 DI6
(SIO)
DXP5 DI4
(SIO)
DXP3 DI2
(SIO)
DXP1 DI0
(SIO)
Process input data valid
0x02 - DVS
14
- DVS
12
- DVS
10
- DVS8 - DVS6 - DVS4 - DVS2 - DVS0
IO-Link process input data
0x03…
0x04
2 words per port
…
0x11…
0x12