Commissioning
Commissioning the device in EtherNet/IP™
94
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Name Data type Description
IOL_Master Error UINT IO-Link master specific, see IO-
Link master Error Codes
IOL_Device Error UINT IO-Link device specific, see IO-
Link device Error Codes and
device documentation
Example:
Read access – name of device at port 4 is read out
Data Value/con-
tent
Description
Class 0x67 IO-Link Parameter Object
Instance 0x01 Addressing the IO-Link master
Instance attribute 0x04 IO-Link port number
Service code 0x4B Read_ISDU: read access
Data Request parameters for the ISDU Read Service
Name Data type
Data byte 0 0x12 UINT
Data byte 1 0x00 UINT
Data byte 2 0x00 USINT
n CIP Service Response:
Name Data type Description
ISDU data Array of Byte
Error-free access:
Content:
54 42 49 4C 2D 4D 31 2D 31 36 44 58 50 (TBIL-
M1-16DXP)
Access error:
Content:
Error code
Write_ISDU – Request
Data Value/content Description
Class 0x67 IO-Link Parameter Object
Instance 0x01 Addressing the IO-Link master
Instance attribute 0x01…n, 128 IO-Link port number, or 128 for Port-0 functions
Service code 0x4C Write_ISDU
Data Request parameters for the ISDU write service
Name Data type Description
Data byte 0 Index (LSB) UINT LSB from index of the IO-Link ISDU object
acc. to IODD
Data byte 1 Index (MSB) UINT MSB from index of the IO-Link ISDU object
acc. to IODD
Data byte 2 Sub index USINT Sub index from the IO-Link ISDU object
acc. to IODD