Parameterizing and Configuring
Parameters_TBEN_S2-4IOL
106
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Parameter name Value Meaning Description
dec. Hex.
Data storage mode Synchronization of parameter data of IO-Link devices (storing the parameter of the connected
device in the master).
If the synchronization is not possible, a diagnostic message is displayed (DS_ERR). In this case
the data memory of the master must be deleted:
Select option "11 = deactivated, delete" to delete the data memory of the master
IO-Link devices in accordance with IO-Link specification V1.0 do not support data storage.
When using IO-Link devices with IO-Link V1.0:
Select option "11 = deactivated, delete" to deactivate data storage.
0 0x00 Activated Synchronization of parameter data activated. The
actual data (master or device) serve as the refer-
ence data.
1 0x01 overwrite Synchronization of parameter data activated, the
data in the master serve as reference data.
2 0x02 read in Synchronization of parameter data activated. The
data in the connected IO-Link device serve as refer-
ence data.
3 0x03 Deactivated, clear
Synchronization of parameter data deactivated.
The data set in the master is deleted.
Activate Quick
Start-Up
For fast applications (e.g. tool changing applications) the start-up time of IO-Link devices can
be shortened. The start-up time defined in the IO-Link specification (TSD = Device Detection
Time) is reduced.
0 0x00 No
The start-up time is within the specified range (0.5
s). All IO-Link devices in accordance with the spe-
cification can be operated.
1 0x01 Yes The start-up time is reduced to approx. 100 ms. It is
not supported by every IO-Link device. It can thus
be necessary to check if the used IO-Link device
starts in this mode.
Device parameter-
ization via GSD
(GSD)
0 0x00 inactive
The port is generic or is not parameterized.
1 0x01 Active In PROFINET the port is parameterized with a spe-
cific device type from the GSDML-file.
Cycle time
0 0x00 Automatic
The lowest cycle time supported by the device is
taken from the table.
1…
191
0x01
0xBF
0.8 = 132,8 ms Settable in steps of 0.8 or 1.6 ms.
255 0xFF Automatic, compatible Compatibility mode The mode solves possible
communication problems with sensors of the SGB
family from IFM.
Revision
0 0x00 Automatic
The Master defines the IO-Link revision automatic-
ally.
1 0x01 V1.0 IO-Link Revision V 1.0 is used.
Process input
data invalid
(PDIN invalid)
0 0x00 Diagnostic generated
If the process data are invalid, a respective dia-
gnostic message is generated.
1 0x01 No diagnostic generated Invalid process data do not cause a diagnostic mes-
sage.
Deactivate
diagnostics
Influences the sending of IO-Link Events from the master to the fieldbus. Depending on the
parameterization, the master transmits Events based on their priority to the fieldbus or not.