Parameter name Value Meaning Description
dec. Hex.
0 0x00 No The master transmits all IO-Link Events to the field-
bus.
1 0x01 Notifications The master transmits all IO-Link Events to the field-
bus except for IO-Link notifications.
2 0x02 Notifications and warnings
The master transmits all IO-Link Events to the field-
bus except for IO-Link notifications and warnings.
3 0x03 Yes The master doesn't transmit any IO-Link Event to
the fieldbus.
Process inpput
data mapping
(Mapping PDIN)
Optimization of the process data mapping for the used fieldbus: The I/O-Link-data can be
swapped depending on the used fieldbus in order to achieve an optimized data mapping on
the fieldbus side.
PROFINET:
With PROFINET, the parameter is permanently set to 0x00 = direct and cannot be changed.
0 0x00 direct
The process data are not swapped.
i.e.: 0x0123 4567 89AB CDEF
1 0x01 Swap 16 bit The bytes are swapped per word.
i.e.: 0x2301 6745 AB89 EFCD
2 0x02 Swap 32 bit The bytes are swapped per double word.
i.e.: 0x6745 2301 EFCD AB89
3 0x03 swap all All bytes are swapped.
i.e.: 0xEFCD AB89 6745 2301
Process output
data mapping
(Mapping PDOUT)
see above Process input data mapping
Vendor ID 0…65535
0x0000…
0xFFFF
Enter the IDs for the port configuration check.
Device ID 0…65535
0x0000…
0xFFFF