Commissioning
Commissioning the device in EtherNet/IP™
90
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Data Value/content Description
Data Request parameters for the ISDU write service
Name Data type Description
0x18 UINT Index for the application specific tag in
the device (e.g. In Turck I/O-Hub TBILM1-
16DXP)
0x00 USINT The index has no sub index.
Byte 0: 0x54
Byte 1: 0x65
Byte 2: 0x6D
Byte 3: 0x70
Byte 4: 0x65
…
Byte 17: 0x31
Byte 18…31: 00
The Application Specific Tag of the device
can consist of 32 byte,
example:
ASCII: Temperature_sensor1
Hex: 54 65 6d 70 65 72 61 74 75 72 65 5f
73 65 6e 73 6f 72 31 00 00…
The remainder of the 32 bytes not re-
quired is filled with 00.
IO-Link master error codes
Error code Designation acc. to
specification
Meaning
0x0000 No error No error
0x7000 IOL_CALL Conflict Unexpected write-request, read request expec-
ted
0x7001 Wrong IOL_CALL Decoding error
0x7002 Port blocked The port is occupied by another task
… reserved
0x8000 The accessed port is occupied by
another task
Timeout, IOL master or IOL device port busy
0x8001 Wrong index Error: IOL index < 32767 or > 65535 selected
0x8002 Wrong port address Port address not available
0x8002 Wrong port function Port function not available
… reserved
IO-Link device error codes
Error code Designation acc. to specification Meaning
0x1000 COM_ERR Communication error
Possible source: the addressed port is paramet-
erized as digital input DI and is not in IO-Link
mode
0x1100 I_SERVICE_TIMEOUT Timeout in communication, device does not re-
spond in time
0x5600 M_ISDU_CHECKSUM Master reports checksum error, access to
device not possible
0x5700 M_ISDU_ILLEGAL Device can not respond to master request
0x8000 APP_DEV Application error in the device
0x8011 IDX_NOTAVAIL Index not available
0x8012 SUBIDX_NOTAVAIL Sub-Index not available