PARAMETER VALUE DESCRIPTION DEFAULT MEMO
r.AP
Opening door delay
1.0”
0.0” - 1’00
Duringtheopeningphase,leaf1muststartmovingbeforeleaf2,toavoid
thatbothdoorsmaycollide.
Leaf2openingwillbedelayedforthesetuptime
r.Ch
Closing door delay
3.0”
0.0” - 1’00
Duringtheclosingphase,leaf1muststartmovingafterleaf2,toavoid
thatbothdoorsmaycollide.
Leaf1closingwillbedelayedforthesetuptime
t.SEr
Lock time
2.0”
0.5”- 1’00
Beforetheopeningphasebegins,thecontrolunitwillenergizetheelectric
lockinordertoreleaseitandenablethegatemotion.t.SEr time will x
theenergizingtime.
m WARNING: in case the gate has no electric lock, set the value
no
no
Function deactivated
SEr.S
Silent Locking Mode
Si
Si
Function activated
no
Function deactivated
t.ASE
Lock advance time
1.0”
0.0”- 1’00
Whiletheelectriclockisenergized,thegatewillstaystandstillfort.ASE
time, to make its release easier.
In case t.ASE is lower than t.SEr,thelockenergizingwillgoonwhile
thedoorswillstartmoving.
mWARNING:incasethegatehasnoelectriclock,setthevalue0.0”
t.inv
Backlash time
no
0.5” - 1’00
Itcouldbeusefultogiveaclosingcommandtomotors,tohelpthe
electric lock release. The control unit controls the motors in reduced power
inclosingdirectionforthesetuptime
no
Function deactivated
t.PrE
Pre-blinking time
1.0”
0.5” - 1’00
Beforeanygatemovement,blinkerwillbeactivatedfort.PrE time, to
warnabouttheincomingmotion
no
Function deactivated
Pot1
Motor 1 power
100
30 - 100
Thedisplayedvalueisthepercentageofmax.motorpower
Pot2
Motor 2 power
100
30 - 100
Thedisplayedvalueisthepercentageofmax.motorpower
Po.r1
Power motor 1 during slow-down phase
50
0 - 70
Thedisplayedvalueisthepercentageofmax.motorpower
Po.r2
Power motor 2 during slow-down phase
50
0 - 70
Thedisplayedvalueisthepercentageofmax.motorpower