PARAMETER VALUE DESCRIPTION DEFAULT MEMO
P.bAt
Maximum motor power during battery operation
Duringbatteryoperation,thecontrollerispoweredwithalowervoltage
comparedtomainspower.Forthisreason,thepowerofthemotorsis
reducedcomparedtonormaloperationandmaynotbesufcienttomove
thegatepanelseffectively.
Thismenuallowsyoutoactivatethemotorsattheirmaximumpower
duringbatteryoperation.
Si
Si
Function activated
no
Function deactivated
SPUn
Start off
Whenthegateisstandstillanditbeginsmoving,theinitialinertiamustbe
faced,therefore,ifyourgateisquiteheavy,itsdoorscouldnotmove.
In case the SPUn(pickup)functionisactivated,fortherst2secondsof
motionofeachdoor,thecontrolunitwillignorebothPot1 and Pot2
valuesanditwillgivemotorsthemaximumpowercommandinorderto
overcomethegateinertia.
Si
Si
Function activated
no
Function deactivated
rAM
Starting ramp
4
0 - 10
In order not to stress too much the motor, when the motion starts the
powerisgraduallyincreased,untilreachedthesetvalueor100%ifthe
take-offisenabled.
Higheristhesetvalue,longerthelengthoftimeoftheramp,thatisthe
timenecessarytoreachthevalueofnominalpower.
SEn1
Enable the obstacle sensor for motor 1
0.0A
0.0A - 14.0A
Thismenuallowsyoutoregulatethesensitivityoftheobstaclesensorfor
motor1.Whenthecurrentabsorbedbythemotorexceedsthesetvalue,
the controller detects an alarm.
Whenthesensorintervenes,thegatestopsandisoperatedinthereverse
directionfor3secondstoremovetheobstacle.
The next start command restarts the movement in the previous direction.
mIfsetto0.0A,thisfunctionisdisabled
m WARNING: if either the limit switches or the slowing down
are disabled, when detected an obstacle the control unit stops the
opening or closing phase without inverting the motion.
SEn2 0.0A - 14.0A
Enable the obstacle sensor for motor 1
0.0A
rAAP
Slow down in opening
25
0 - 100
Thismenuallowsregulatingthepercentageoftheride/drivethatiscarried
outatreducedspeedduringthelastopeningstretch
rACh
Slow down in closing
25
0 - 100
Thismenuallowsregulatingthepercentageoftheride/drivethatiscarried
outatreducedspeedduringthelastclosingstretch
t.CvE
Fast closing time after slowing down
0.0”
0.0” - 3.0”
Ifaslowingtimeotherthan0issetup,itcouldbelikelythatthegate
speedisnotenoughforthelocktofastenduringtheclosingphase.
Incasethisfunctionisenabled,oncetheslowingdownphaseisnished,
thecontrolunitwillgiveanormalspeedcommand(thatistosay,withno
slowingdown)forthesetuptime.
m WARNING: in case the gate has no electric lock,
set the value 0.