Table 65: General protections settings
Index Parameter Min Max Unit Default ID Description
P3.9.1.15
Startup Prevented
Fault
0 1 0 15593
0 = Fault
1 = No action
Table 66: Motor thermal protection settings
Index Parameter Min Max Unit Default ID Description
P3.9.2.1
Motor Thermal Pro-
tection
0 3 2 704
0 = No action
1 = Alarm
2 = Fault (Stop by stop
mode)
3 = Fault (Stop by
coasting)
P3.9.2.2
Ambient Tempera-
ture
-20.0 100.0 °C 40.0 705
P3.9.2.3
Zero Speed Cooling
Factor
5.0 150.0 % Varies 706
P3.9.2.4
Motor Thermal Time
Constant
1 200 min Varies 707
P3.9.2.5
Motor Thermal Load-
ability
10 150 % 100 708
Table 67: Motor stall protection settings
Index Parameter Min Max Unit Default ID Description
P3.9.3.1 Motor Stall Fault 0 3 0 709
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
P3.9.3.2 Stall Current 0.00 5.2 A 3.7 710
P3.9.3.3 Stall Time Limit 1.00 120.00 s 15.00 711
P3.9.3.4 Stall Frequency Limit 1.00 P3.3.1.2 Hz 25.00 712